The serial essernet interface can be used as a gateway to link remote computers that support the ESSER data protocol (EDP). The EDP version (bidirectional) is only provided with information from the essernet, with remote control options e.g. for the connection to a Building Management System (BMS). The unit includes a slot for an essernet module and is therefore a fully functional unit within the short circuit and open circuit resistant essernet.
| Operating voltage | 10.5 ... 28 V DC |
| Current consumption @ 12 V DC | approx. 60 mA |
| Ambient temperature | -5 °C ... 50 °C |
| Storage temperature | -10 °C ... 50 °C |
| Air humidity | < 95 % (non condensing) |