Esser Fire Systems | Esser Management System | Esser Voice Alarms | Esser Loudspeakers | Gent Analoque Addressable | Gent Detection & Alarm Devices | Gent Interfaces | Gent Text & Graphic Software |
ESSER » Fire Systems » Automatic Detectors » Intrinsically Safe » O2T multisensor fire detector IQ8Quad Ex (i) w/o isolator

O2T multisensor fire detector IQ8Quad Ex (i) w/o isolator

Intelligent detector with two integrated optical smoke sensors with different scattered-light angles as well as additional heat detector sensor evaluation for the recognition of smoldering fires up to open fires with uniform characteristics. Comparison of the heat sensor signals for smoke classification and reduction of false alarms by interferences, e.g. from steam or dust. Due to its excellent detection characteristics, and enhanced false alarm management, the detector is also able to recognize TF1 and TF6 test fires, described in the standards. The O²T intelligent detector is also suitable for a higher operating temperature of up to +65 °C. Used when early and reliable fire detection is requested. Intelligent fire detector with decentralized intelligence, automatic function self-test, emergency mode, storage of alarm and operating data, alarm display. Soft addressing and separate operational display is only possible when operating an esserbus / esserbus-PLus IQ8Quad detector without loop isolator, especially for usage in explosion zones. Operation with individual addressing at Ex barrier Part No. 804744 and as standard detector at Ex barrier Part No. 764744. Consider that the change of parameter settings for environmental adaption is reserved to the Non-Ex automatic detectors.

 

Part No.   :   803374.EX


Features

There is no feature at the moment.

Technical Data

Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC  approx. 60 μA
Alarm current @ 9 V DC typ. 18 mA
Area to be monitored max. 110 m²
Height to be monitored max. 12 m
Ambient temperature (Ta)  -20 °C ... 70 °C
Application temperature  -20 °C ... 65 °C
Storage temperature  -25 °C ... 75 °C
Max. Output current (Io 10 mA
Max. Input Voltage (Ui 21 V DC
Max. Input current (Ii 252 mA
Max. internal capacity (Ci)  1 nF
Explosion protection Ex ib IIC T4 Gb 
Type of protection IP 43 (incl. base + option)
Material  ABS
Air humidity   < 95 % (non condensing) 
Color white, similar to RAL 9010 
Weight approx. 110 g
Detector specification EN 54-7:2006/-5B:2000/A1:2002, CEA 4021
EC-type examination certificate TÜV 09 ATEX 554910
Dimensions  Ø: 117 mm H: 49 mm (62 mm incl. base)